The Auxiliary relay has normally open / normally closed contacts, and is configurable for energized or de-energized operation, and latching or non-latching operation. 0 to 20 mA Output A 0 to 20 mA output is available as an option (in addition to the three relays). This option provides a 0 to 20 mA dc current output for transmitting detector status information to other devices. The circuit can be wired in either an isolated or non-isolated configuration and can drive a maximum loop resistance of 500 ohms from 18 to 19.9 Vdc and 600 ohms from 20 to 30 Vdc. Table 1 indicates the detector status conditions represented by the various current levels. The output is calibrated at the factory, with no need for field calibration. A model with relays and 0-20 mA with HART is also available. Refer to Addendum number 95-8636 for complete details. NOTE The output of the 0 to 20 mA current loop is not monitored by the fault detection circuitry of the X5200. Therefore, an open circuit on the loop will not cause the fault relay to change state or the detector status LED to indicate a fault. The status of the LED always follows the status of the relays. An alarm condition will normally over-ride a fault condition, unless the nature of the fault condition impairs the ability of the detector to generate or maintain an alarm output, i.e. loss of operating power. LON/SLC Output The EQP model is designed for use exclusively with the Det-Tronics Eagle Quantum Premier system. The detector communicates with the system controller over a digital communication network or LON/SLC (Local Operating Network / Signaling Line Circuit). The LON/ SLC is a fault tolerant, two wire digital communication network arranged in a loop configuration. Analog and relay outputs are not available on this model. LED A tri-color LED on the detector faceplate indicates normal condition and notifies personnel of fire alarm or fault conditions. Table 2 indicates the condition of the LED for each status. Attention The X5200 contains a source tube that is filled with a gas mixture containing Krypton 85 (Kr85), a radioactive material. Radioactive materials are subject to regulation under U.S. and international law. oi (Optical Integrity) Automatic oi The X5200 includes the Automatic oi feature — a calibrated performance test that is automatically performed once per minute to verify complete detector operation capabilities. No testing with an external test lamp is required. The detector automatically performs the same test that a maintenance person with a test lamp would perform — once every minute, 60 times per hour. However, a successful Automatic oi test does not produce an alarm condition. Table 1—Detector Status Conditions Indicated by Current Level Current Level (±0.3 mA) Detector Status 0 mA Power Fault 1 mA General Fault 2 mA oi Fault 4 mA Normal Operation 8 mA IR Pre-Alarm only 12 mA UV Alarm only 14 mA IR Alarm only 16 mA Pre-Alarm 20 mA Fire Alarm Table 2—Detector Status Indicator Detector Status LED Indicator Power On/Normal Auto oi (no fault or fire alarm) Green Power On/Normal Man oi Green, flashing off for 0.5 sec. every 5 sec. Fault Yellow UV Alarm only Red, flashing on for 0.5 sec. and off for 0.5 sec. IR Alarm only Red, flashing on for 0.25 sec. and off for 0.25 sec. Pre-Alarm Red, flashing on for 1 sec. and off for 1 sec. Fire (Alarm) Steady Red On Power-Up, The LED Flashes in Sequence as Follows, Indicating Sensitivity and Signal Processing Status Low UV Sensitivity Medium UV Sensitivity High UV Sensitivity Very High UV Sensitivity One Red Flash Two Red Flashes Three Red Flashes Four Red Flashes Stand. UV Signal Process. Arc Rej. UV Signal Process. One Yellow Flash Two Yellow Flashes Low IR Sensitivity Medium IR Sensitivity High IR Sensitivity Very High IR Sensitivity One Green Flash Two Green Flashes Three Green Flashes Four Green Flashes Quick Fire/TDSA IR Signal TDSA only IR Signal One Yellow Flash Two Yellow Flashes 13.1 3 95-8546 The X5200 signals a fault condition when less than half of the detection range remains. This is indicated by the Fault output and is evident by the yellow color of the LED on the face of the detector. See the "Troubleshooting" section for further information. Magnetic oi / Manual oi The detector also incorporates both Magnetic oi (Mag oi) and Manual oi (Man oi) features that provide the same calibrated test as the Automatic oi, and in addition actuates the Alarm output to verify operation for preventive maintenance requirements. These features can be performed at any time and eliminate the need for testing with a non-calibrated external test lamp. CAUTION These tests require disabling of all extinguishing devices to avoid release resulting from a successful test. The Mag oi test is performed by placing a magnet at the location marked "MAG OI" on the outside of the detector (see Figure 2). The Man oi test is accomplished by connecting the oi lead (terminal 22) to power supply minus via an external switch. The magnet or switch must be held in place for a minimum of 6 seconds to complete the test. Either of these test methods activates the calibrated UV and IR emitters. If the resulting signal meets the test criteria, indicating that greater than half of the detection range remains, the Alarm output changes state, the indicating LED changes to red, and the 0-20 mA current output goes to 20 mA. This condition remains until the magnet is removed or the switch is released, regardless of whether the relays are set for latching or non-latching operation. If less than half of the detection range remains, no alarm is produced and a fault is generated. The fault indication can be reset by momentarily applying the Mag oi or Man oi switch. NOTE Refer to Appendix A for FM verification of the oi function. Communication The X5200 is furnished with an RS-485 interface for communicating status and other information with external devices. The RS-485 supports MODBUS protocol, with the detector configured as a slave device. For HART communication, connect a HART communicator across a 250 ohm resistor in the 0-20 mA loop. NOTE The EQP model uses LON/SLC communication. RS-485 and HART communication are not available on the EQP model. Data Logging Data logging capability is also provided. Status conditions such as normal, power down, general and oi faults, pre-alarm, fire alarm, time and temperature are recorded. Each event is time and date stamped, along with the temperature and input voltage. Event data is stored in non-volatile memory when the event becomes active, and again when the status changes. Data is accessible using the Inspector Connector accessory, RS-485, or the EQP Controller. Integral Wiring Compartment All external wiring to the device is connected within the integral junction box. The detector is furnished with four conduit entries, with either 3/4 inch NPT or M25 threads. Signal Processing Options The X5200 features signal processing options for both the UV and IR sensor. These options determine the type of logic that the detector will use for processing fire signals to customize the X5200 to the application. IR Detector Options The IR detector in the X5200 can be programmed for: –– TDSA enabled –– Both TDSA and Quick Fire enabled (either initiates fire alarm) Time Domain Signal Analysis (TDSA) The TDSA signal processing technique analyzes the input signal in real time, requiring the IR signal to flicker randomly in order to recognize it as a fire condition. Using TDSA signal processing, the X5200 ignores regularly chopped blackbody sources (occurring in areas where moving conveyors and hot objects in proximity to one another result in a regularly chopped IR signal), because it looks for a less uniform signal. However, in the presence of a regularly chopped signal, the detector is more susceptible to false alarms due to sporadic IR that functions as a trigger when occurring in conjunction with the regularly chopped signal. 13.1 4 95-8546 Quick Fire (High Speed) The Quick Fire (High Speed) feature can be used in conjunction with the TDSA signal processing method. This method overrides TDSA requirements in the event of a sudden and intense signal, such as the result of a flash fire. When Quick Fire is activated, the detector is capable of responding to an intense fire signal in less than 30 milliseconds (0.030 seconds). Using the Quick Fire feature in conjunction with TDSA signal processing allows the detector to provide a high speed response to a large, non-flickering fire (such as in high pressure gas applications). Additionally, when the Quick Fire feature and TDSA signal processing are used in conjunction, the detector maintains an ability to respond to fires that start very small and grow in size and intensity over time. UV Detector Options The UV detector output (measured in counts per second) is compared to the fire threshold (the “sensitivity” setting). If the radiant energy level from the fire exceeds the selected alarm threshold level, the fire alarm output is activated. In every application, it is crucial to ensure that the radiant ultraviolet energy level from the expected fire at the required distance from the detector will exceed the selected sensitivity level. The UV detector in the X5200 can be programmed for: ––Arc Rejection –– Standard Signal Processing Arc Rejection The Arc Rejection mode enables the detector to prevent nuisance fire alarms caused by UV from shortduration electrical arcs or electrostatic discharge, while maintaining the ability to reliably detect the UV radiation given off by a flame. Typical applications that benefit from arc rejection logic include electrostatic coating processes and uncontrolled environments where transient UV sources can be present, such as many typical outdoor applications. Most false alarm sources have short transient UV signatures, while fire creates a long UV signature over many seconds. Most fires are detected in a few seconds (see response times in Appendix A). Standard Signal Processing Standard signal processing is recommended for highspeed suppression systems only. To allow for high-speed operation, the standard processing mode does not incorporate the arc rejection programming. This mode should only be used in a controlled, indoor environment. General Application Information Response Characteri stics Response is dependent on the detector's sensitivity setting, arc rejection, and time delay settings. Other factors include distance, type of fuel, temperature of the fuel, and time required for the fire to come to equilibrium. As with all fire tests, results must be interpreted according to an individual application. See Appendix A for third-party approved fire test results. Additional fire test results are available from Det-Tronics. Welding Electric arc welding is a source of intense ultraviolet radiation. UV radiation from arc welding readily scatters and can deflect across significant distances, even when direct obstructions exist. Any open door or window can allow nuisance UV radiation from arc welding to enter an enclosed area, causing a possible response from the UV detector. It is recommended that the system be bypassed during welding operations in situations where the possibility of a false alarm cannot be tolerated. Gas welding mandates system bypass, since the gas torch is an actual fire. Arc welding rods can contain organic binder materials in the flux that burn during the welding operation and are detectable by the X5200. Welding rods with clay binders do not burn and will not be detected by the X5200. However, system bypass is always recommended, since the material being welded may be contaminated with organic substances (paint, oil, etc.) that will burn and possibly cause the X5200 to alarm. Artificial Lighting The X5200 should not be located within 3 feet (0.9 m) of artificial lights. Excess heating of the detector could occur due to heat radiating from the lights. EMI/RFI Interference The X5200 is resistant to interference by EMI and RFI, and is EMC Directive compliant and CE marked. It will not respond to a 5 watt walkie-talkie at distances greater than 1 foot (0.3 m). Non-Carbon Fires The response of the X5200 is limited to carbonaceous fuels. It should not be used to detect fires from fuels that do not contain carbon, such as hydrogen, sulfur and burning metals. 13.1 5 95-8546 False Alarm Sources UV: The UV sensor is solar blind to the ultraviolet component of solar radiation. However, it may respond to sources of UV besides fire, such as arc flash, electric arc welding, grinding metal, lightning, high voltage corona, x-rays, and gamma radiation. NOTE Radiation generated by false alarm sources such as periodic lightning or sparks in the area may be effectively ignored by the detector using the arc rejection feature or time delay. IR: The detector has been designed to ignore steady state infrared